Artekis uses AI to look through the process data already in your Ignition gateway (history, alarms and production records) and tells you what is about to cost you, with the evidence.
LS-4 Pump 1 moves about 12% less flow per amp in its last 170 runs than in its 1,460 runs of Sep 24 to Oct 19: about 280 gpm at 6.5 A, against 320 gpm at 6.5 A, while Pump 2 is unchanged (within 1%). Its runs also got longer (4 minutes against 3.5 minutes), so it runs more hours for the same water.
Redrawn from the live finding, Nov 9, 2026. Open the real finding
Less flow at the same or higher current, on one pump but not its twin, is the pattern of a worn or partly blocked impeller or wear ring; no alarm covers it.
Plan an inspection of LS-4 Pump 1: pull it and check the impeller and wear ring for wear or a partial blockage, and compare its run times with its twin’s.
Put LS-4 Pump 1 on a set impeller and wear-ring inspection interval, and log its flow per amp after each overhaul so the next loss shows up early.
Final effluent turbidity has been climbing steadily since Oct 28, from about 1.55 NTU to about 3.4 NTU by Nov 8, about 1.8 NTU above its earlier level.
Redrawn from the live finding, Nov 9, 2026. Open the real finding
The trend is steady and well outside the normal spread of the reading. No alarm limit or normal range is set for this reading, so no one has stated which direction is dangerous; someone who knows the process should say whether a higher turbidity is the risk here.
Check the effluent turbidity reading against a grab sample and confirm the analyzer is clean and calibrated. Ask the operator who knows the process whether anything changed around Oct 28 to Nov 1.
Set an alarm limit and normal range for Final effluent turbidity so the rise is flagged before it runs this long.
DCM-204 metal temperature ran outside its setpoint band 23% of running time on part WD-4520-VB in the last 24 hours, up from 1% in its baseline (Oct 19 to Nov 6); on average 2 °F under setpoint (setpoint about 1250 °F).
Redrawn from the live finding, Nov 9, 2026. Open the real finding
A setpoint change the reading follows is not flagged; a reading that leaves a setpoint that did not move is. Cost, estimated: $9,258 of scrap and downtime above this press’s own normal since it began.
Check why DCM-204 is not holding metal temperature at its setpoint: compare the reading with a hand-held or second instrument, then look at what controls it (heater or furnace, valve, pump, accumulator charge) before changing the setpoint or the setup sheet.
Keep the instrument on its calibration schedule, and log setpoint changes with their reason so a deliberate change is easy to tell from a drift.
The RS-4 raw milk silo temperature fell about 2.4 °F from Oct 25 and has held near 34.3 °F since about Nov 3. The silo holds milk during this period.
Redrawn from the live finding, Nov 9, 2026. Open the real finding
No alarm limit or normal range is set for this reading, and no one has said which direction is dangerous, so Artekis cannot say whether the change matters for the milk. If the probe has drifted, the milk is about 2.4 °F warmer than the screen shows.
Ask the process owner whether a silo temperature near 34.3 °F is expected for the milk it holds, and check that the RS-4 temperature sensor reads correctly.
Set a normal range and alarm limits for the RS-4 raw milk silo temperature, and record which direction is dangerous for this reading, so future drifts are judged against a known target.
The CIP-1 caustic strength Low alarm activated 1,271 times in the week, and 154 bursts of chatter held 587 of those activations (46.2%).
Redrawn from the live finding, Nov 9, 2026. Open the real finding
The alarm trips below 30.0 with a deadband of 0.0 and no on-delay or clear delay, so a value hovering near the setpoint re-triggers it repeatedly. 78 of 998 active 10-minute periods exceeded the threshold of 10 activations; the peak was 19.
Check the CIP-1 caustic strength reading for noise or a value sitting near 30.0, and acknowledge the repeat alarms knowing they are one condition.
On the UDT type member CausticStrength|Low, add a clear delay of 15 s and a deadband, so the value must move back past the setpoint before the alarm clears. Check the effect on CIP-2, which shares the type.
Four findings from plants running Artekis, each shown on the finding screen your team would use.
The same module runs on every plant. What changes is what it watches and what a miss costs you.
It watches every measurement against its own normal, reviews your alarms, explains stops, checks the gateway, and answers questions in plain English. Every finding lands on one list in Perspective, in plain words, with the machine it is about, what to do now and the evidence behind it. Each change is a recommendation; your engineers decide what to apply.
Your supervisors type a question beside the Perspective screens they already use. The answer comes back in minutes and dollars, with the records behind every claim. An answer that cannot cite its source says so instead of guessing.

Both answers are from a die-casting plant running Artekis. Ask reads your production database only through named queries your team writes, so IT decides exactly what it can see.
Artek is an Ignition integrator and an Inductive Automation Premier Integrator, founded in 2020 by Jerry Eppler and Jae Park, both former Inductive Automation engineers. We build the kind of Ignition systems Artekis analyzes, for water utilities, data centers, manufacturers and energy companies.
One license covers every analysis on one gateway, with annual support for updates, the same model as Ignition. It includes four hours of an Artek engineer’s time to install it with your team, draft your plant model, run your first reports, and show your supervisors how to ask questions it answers well. There is no cloud service to subscribe to; model usage is paid to your provider, in cents.
Annual support is 20% of what you paid for the license, so $1,400 a year on a 2026 purchase instead of $2,000.
Artekis is read-only. It reads tags, history, alarms and the audit log, and writes its findings to its own tables in your database. A proposed change is a recommendation your team applies under its own change control.
Yes, through named queries. Your team writes a select-type named query in a project Artekis is allowed to read, and Ask can call it, up to 1,000 rows at a time. Ask runs only those queries, so your IT team decides exactly what the model can see.
One you choose, through your own key: Anthropic, OpenAI, or any OpenAI-compatible endpoint, including a model you run on your own network. Every call is priced and recorded.
Copilot works on Microsoft 365 data and cannot see an Ignition gateway. Artekis runs inside the gateway and reads your tags, history, alarms, audit log and production database directly, then sends only the evidence for one question or one run to the model you choose. It answers in Perspective, where your supervisors already are, with a citation for each claim.
Ignition 8.3. The module loads on 8.3.4 and later, and 8.3.8 is the verified platform.
A one-time license per gateway, normally $10,000 and $7,000 for purchases through December 31, 2026, activated through Ignition’s own licensing, with an annual support plan for updates and new releases, the same model as Ignition. The price includes four hours of an Artek engineer’s time to set it up with your team. You can evaluate it in Ignition’s two-hour trial first, and it is free on Maker Edition under Maker’s non-commercial terms.
A member of our team reads every message and replies, usually the same day.
Contact us →