Intelligence, securely applied to your plant.

Catch what your alarms miss, before it turns into costly downtime.

Artekis uses AI to look through the process data already in your Ignition gateway (history, alarms and production records) and tells you what is about to cost you, with the evidence.

Artekis findingsFrom three plants running Artekis. Select a finding to see the evidence.
High Lift station pump moving 12% less water Water 12% less flow per amp

What was found

LS-4 Pump 1 moves about 12% less flow per amp in its last 170 runs than in its 1,460 runs of Sep 24 to Oct 19: about 280 gpm at 6.5 A, against 320 gpm at 6.5 A, while Pump 2 is unchanged (within 1%). Its runs also got longer (4 minutes against 3.5 minutes), so it runs more hours for the same water.

The evidence

Pump 1 now moves 12% less water for the same powerFlow per amp of LS-4 Pump 1, median per day of its runsHigher is better. A healthy pump holds a flat line: Pump 2, its twin, is unchanged (within 1%). The date is from Artekis checking this plant’s history when it was set up.
4244464850Water moved per amp of motor current (gpm/A)Oct 12Oct 16Oct 20Oct 24Oct 28Nov 1Nov 5Oct 11: 49.8 gpm per ampOct 12: 49.7 gpm per ampOct 13: 49.6 gpm per ampOct 14: 49.1 gpm per ampOct 15: 49.0 gpm per ampOct 16: 48.7 gpm per ampOct 17: 48.5 gpm per ampOct 18: 48.1 gpm per ampOct 19: 47.9 gpm per ampOct 20: 47.7 gpm per ampOct 21: 47.3 gpm per ampOct 22: 47.1 gpm per ampOct 23: 46.7 gpm per ampOct 24: 46.4 gpm per ampOct 25: 46.2 gpm per ampOct 26: 45.9 gpm per ampOct 27: 45.6 gpm per ampOct 28: 45.3 gpm per ampOct 29: 44.9 gpm per ampOct 30: 44.5 gpm per ampOct 31: 44.1 gpm per ampNov 1: 43.8 gpm per ampNov 2: 43.6 gpm per ampNov 3: 43.5 gpm per ampNov 4: 43.5 gpm per ampNov 5: 43.6 gpm per ampNov 6: 43.6 gpm per ampNov 7: 43.6 gpm per ampNov 8: 43.7 gpm per ampNormal: about 320 gpm at 6.5 A (its runs of Sep 24 to Oct 19)12% less waterabout 280 gpm now, for the same 6.5 ANo alarm is set on this reading.Artekis catches it here: Oct 224244464850Water moved per amp (gpm/A)Oct 12Oct 21Oct 30Nov 8Oct 11: 49.8 gpm per ampOct 12: 49.7 gpm per ampOct 13: 49.6 gpm per ampOct 14: 49.1 gpm per ampOct 15: 49.0 gpm per ampOct 16: 48.7 gpm per ampOct 17: 48.5 gpm per ampOct 18: 48.1 gpm per ampOct 19: 47.9 gpm per ampOct 20: 47.7 gpm per ampOct 21: 47.3 gpm per ampOct 22: 47.1 gpm per ampOct 23: 46.7 gpm per ampOct 24: 46.4 gpm per ampOct 25: 46.2 gpm per ampOct 26: 45.9 gpm per ampOct 27: 45.6 gpm per ampOct 28: 45.3 gpm per ampOct 29: 44.9 gpm per ampOct 30: 44.5 gpm per ampOct 31: 44.1 gpm per ampNov 1: 43.8 gpm per ampNov 2: 43.6 gpm per ampNov 3: 43.5 gpm per ampNov 4: 43.5 gpm per ampNov 5: 43.6 gpm per ampNov 6: 43.6 gpm per ampNov 7: 43.6 gpm per ampNov 8: 43.7 gpm per ampNormal: 320 gpm at 6.5 A12% lesswaterNo alarmset on thisCaught Oct 22

Redrawn from the live finding, Nov 9, 2026. Open the real finding

Why it matters

Less flow at the same or higher current, on one pump but not its twin, is the pattern of a worn or partly blocked impeller or wear ring; no alarm covers it.

What to do now

Plan an inspection of LS-4 Pump 1: pull it and check the impeller and wear ring for wear or a partial blockage, and compare its run times with its twin’s.

How to prevent it

Put LS-4 Pump 1 on a set impeller and wear-ring inspection interval, and log its flow per amp after each overhaul so the next loss shows up early.

Medium Treated water turning cloudy, caught within 2 days Water caught at 2.1 NTU

What was found

Final effluent turbidity has been climbing steadily since Oct 28, from about 1.55 NTU to about 3.4 NTU by Nov 8, about 1.8 NTU above its earlier level.

The evidence

The treated water got cloudier and stayed that way, with no alarmFinal effluent turbidity, 12-hour mediansLower is better: turbidity is how cloudy the treated water is. It read about 1.55 NTU for weeks. The date is from Artekis checking this plant’s history when it was set up.
1234Treated water turbidity (NTU). Lower is clearer.Oct 12Oct 16Oct 20Oct 24Oct 28Nov 1Nov 5Oct 11: 1.57 NTUOct 12: 1.56 NTUOct 12: 1.56 NTUOct 13: 1.56 NTUOct 13: 1.56 NTUOct 14: 1.55 NTUOct 14: 1.55 NTUOct 15: 1.55 NTUOct 15: 1.55 NTUOct 16: 1.55 NTUOct 16: 1.55 NTUOct 17: 1.54 NTUOct 17: 1.55 NTUOct 18: 1.55 NTUOct 18: 1.55 NTUOct 19: 1.55 NTUOct 19: 1.55 NTUOct 20: 1.55 NTUOct 20: 1.56 NTUOct 21: 1.55 NTUOct 21: 1.55 NTUOct 22: 1.55 NTUOct 22: 1.55 NTUOct 23: 1.55 NTUOct 23: 1.55 NTUOct 24: 1.71 NTUOct 24: 1.57 NTUOct 25: 1.55 NTUOct 25: 1.55 NTUOct 26: 1.55 NTUOct 26: 1.55 NTUOct 27: 1.55 NTUOct 27: 1.55 NTUOct 28: 1.55 NTUOct 28: 1.56 NTUOct 29: 1.56 NTUOct 29: 1.68 NTUOct 30: 2.08 NTUOct 30: 1.98 NTUOct 31: 2.06 NTUOct 31: 2.29 NTUNov 1: 2.36 NTUNov 1: 2.52 NTUNov 2: 2.66 NTUNov 2: 2.88 NTUNov 3: 3.58 NTUNov 3: 3.29 NTUNov 4: 3.31 NTUNov 4: 3.37 NTUNov 5: 3.39 NTUNov 5: 3.42 NTUNov 6: 3.44 NTUNov 6: 3.45 NTUNov 7: 3.43 NTUNov 7: 3.43 NTUNov 8: 3.42 NTUNormal: about 1.55 NTUNo alarm is set on this reading.About 1.8 NTU above normal1.55 then, about 3.4 nowArtekis catches it here: Oct 30, at 2.1 NTU1234Turbidity (NTU)Oct 12Oct 21Oct 30Nov 8Oct 11: 1.57 NTUOct 12: 1.56 NTUOct 12: 1.56 NTUOct 13: 1.56 NTUOct 13: 1.56 NTUOct 14: 1.55 NTUOct 14: 1.55 NTUOct 15: 1.55 NTUOct 15: 1.55 NTUOct 16: 1.55 NTUOct 16: 1.55 NTUOct 17: 1.54 NTUOct 17: 1.55 NTUOct 18: 1.55 NTUOct 18: 1.55 NTUOct 19: 1.55 NTUOct 19: 1.55 NTUOct 20: 1.55 NTUOct 20: 1.56 NTUOct 21: 1.55 NTUOct 21: 1.55 NTUOct 22: 1.55 NTUOct 22: 1.55 NTUOct 23: 1.55 NTUOct 23: 1.55 NTUOct 24: 1.71 NTUOct 24: 1.57 NTUOct 25: 1.55 NTUOct 25: 1.55 NTUOct 26: 1.55 NTUOct 26: 1.55 NTUOct 27: 1.55 NTUOct 27: 1.55 NTUOct 28: 1.55 NTUOct 28: 1.56 NTUOct 29: 1.56 NTUOct 29: 1.68 NTUOct 30: 2.08 NTUOct 30: 1.98 NTUOct 31: 2.06 NTUOct 31: 2.29 NTUNov 1: 2.36 NTUNov 1: 2.52 NTUNov 2: 2.66 NTUNov 2: 2.88 NTUNov 3: 3.58 NTUNov 3: 3.29 NTUNov 4: 3.31 NTUNov 4: 3.37 NTUNov 5: 3.39 NTUNov 5: 3.42 NTUNov 6: 3.44 NTUNov 6: 3.45 NTUNov 7: 3.43 NTUNov 7: 3.43 NTUNov 8: 3.42 NTUNormal: about 1.55 NTUNo alarm set on this reading1.8 NTUabove normalCaught Oct 30

Redrawn from the live finding, Nov 9, 2026. Open the real finding

Why it matters

The trend is steady and well outside the normal spread of the reading. No alarm limit or normal range is set for this reading, so no one has stated which direction is dangerous; someone who knows the process should say whether a higher turbidity is the risk here.

What to do now

Check the effluent turbidity reading against a grab sample and confirm the analyzer is clean and calibrated. Ask the operator who knows the process whether anything changed around Oct 28 to Nov 1.

How to prevent it

Set an alarm limit and normal range for Final effluent turbidity so the rise is flagged before it runs this long.

Medium Metal temperature outside its band 23% of the time Die casting $9,258 of scrap

What was found

DCM-204 metal temperature ran outside its setpoint band 23% of running time on part WD-4520-VB in the last 24 hours, up from 1% in its baseline (Oct 19 to Nov 6); on average 2 °F under setpoint (setpoint about 1250 °F).

The evidence

The metal temperature ran outside its band 23% of the time. It was 1%.Gap of DCM-204 metal temperature to its setpoint, each running 5-minute step, latest 24 hoursInside the band is good. The reading stayed inside every per-shot warning limit and outside its own setpoint band. Artekis first flagged it on Nov 7.
-15-10-50+5Metal temperature minus its setpoint (°F). 0 is on setpoint.5 PM, Nov 89 PM1 AM, Nov 95 AM9 AM1 PMAllowed band: setpoint ±5 °FOutside the band 23% of running time. It was 1%.The bars along the bottom mark the time outside the band. No alarm fired.-15-10-50+5Metal temperature minus setpoint (°F)5 PM, Nov 85 AM, Nov 9Allowed band: ±5 °FOutside the band23% of running time.It was 1%.

Redrawn from the live finding, Nov 9, 2026. Open the real finding

Why it matters

A setpoint change the reading follows is not flagged; a reading that leaves a setpoint that did not move is. Cost, estimated: $9,258 of scrap and downtime above this press’s own normal since it began.

What to do now

Check why DCM-204 is not holding metal temperature at its setpoint: compare the reading with a hand-held or second instrument, then look at what controls it (heater or furnace, valve, pump, accumulator charge) before changing the setpoint or the setup sheet.

How to prevent it

Keep the instrument on its calibration schedule, and log setpoint changes with their reason so a deliberate change is easy to tell from a drift.

Medium Silo reading dropped 2.4 °F and stayed there Dairy no alarm set on it

What was found

The RS-4 raw milk silo temperature fell about 2.4 °F from Oct 25 and has held near 34.3 °F since about Nov 3. The silo holds milk during this period.

The evidence

The silo reading dropped 2.4 °F and stayed there, with no alarmRS-4 raw milk silo temperature, 12-hour mediansA steady reading is normal. Milk or probe? One sensor cannot say, so Artekis flagged the step against the probe’s own history.
333435363738Silo temperature reading (°F)Oct 13Oct 17Oct 21Oct 25Oct 29Nov 2Nov 6Oct 12: 36.6 °FOct 13: 36.3 °FOct 13: 36.4 °FOct 14: 37.9 °FOct 14: 36.4 °FOct 15: 36.4 °FOct 15: 36.5 °FOct 16: 37.0 °FOct 16: 36.5 °FOct 17: 36.5 °FOct 18: 36.6 °FOct 18: 36.4 °FOct 19: 36.4 °FOct 19: 38.1 °FOct 20: 36.5 °FOct 20: 36.5 °FOct 21: 36.6 °FOct 21: 37.2 °FOct 22: 36.5 °FOct 22: 36.6 °FOct 23: 36.6 °FOct 24: 36.3 °FOct 24: 36.4 °FOct 25: 37.6 °FOct 25: 36.4 °FOct 26: 36.4 °FOct 26: 36.5 °FOct 27: 36.8 °FOct 27: 36.0 °FOct 28: 35.9 °FOct 29: 35.9 °FOct 29: 35.5 °FOct 30: 35.5 °FOct 30: 36.4 °FOct 31: 35.0 °FOct 31: 34.9 °FNov 1: 34.9 °FNov 1: 35.3 °FNov 2: 34.5 °FNov 2: 34.4 °FNov 3: 34.3 °FNov 4: 34.1 °FNov 4: 34.1 °FNov 5: 35.6 °FNov 5: 34.1 °FNov 6: 34.1 °FNov 6: 34.2 °FNov 7: 34.6 °FNov 7: 34.0 °FNov 8: 34.1 °FNov 9: 34.3 °FNo alarm is set on this reading.Before Oct 25: about 36.7 °FDropped 2.4 °Fand stayedSince Nov 3: about 34.3 °FArtekis catchesit here: Nov 7333435363738Silo temperature reading (°F)Oct 13Oct 22Oct 31Nov 9Oct 12: 36.6 °FOct 13: 36.3 °FOct 13: 36.4 °FOct 14: 37.9 °FOct 14: 36.4 °FOct 15: 36.4 °FOct 15: 36.5 °FOct 16: 37.0 °FOct 16: 36.5 °FOct 17: 36.5 °FOct 18: 36.6 °FOct 18: 36.4 °FOct 19: 36.4 °FOct 19: 38.1 °FOct 20: 36.5 °FOct 20: 36.5 °FOct 21: 36.6 °FOct 21: 37.2 °FOct 22: 36.5 °FOct 22: 36.6 °FOct 23: 36.6 °FOct 24: 36.3 °FOct 24: 36.4 °FOct 25: 37.6 °FOct 25: 36.4 °FOct 26: 36.4 °FOct 26: 36.5 °FOct 27: 36.8 °FOct 27: 36.0 °FOct 28: 35.9 °FOct 29: 35.9 °FOct 29: 35.5 °FOct 30: 35.5 °FOct 30: 36.4 °FOct 31: 35.0 °FOct 31: 34.9 °FNov 1: 34.9 °FNov 1: 35.3 °FNov 2: 34.5 °FNov 2: 34.4 °FNov 3: 34.3 °FNov 4: 34.1 °FNov 4: 34.1 °FNov 5: 35.6 °FNov 5: 34.1 °FNov 6: 34.1 °FNov 6: 34.2 °FNov 7: 34.6 °FNov 7: 34.0 °FNov 8: 34.1 °FNov 9: 34.3 °FNo alarm set on this readingBefore: about 36.7 °FCaught Nov 7Dropped 2.4 °F and stayed

Redrawn from the live finding, Nov 9, 2026. Open the real finding

Why it matters

No alarm limit or normal range is set for this reading, and no one has said which direction is dangerous, so Artekis cannot say whether the change matters for the milk. If the probe has drifted, the milk is about 2.4 °F warmer than the screen shows.

What to do now

Ask the process owner whether a silo temperature near 34.3 °F is expected for the milk it holds, and check that the RS-4 temperature sensor reads correctly.

How to prevent it

Set a normal range and alarm limits for the RS-4 raw milk silo temperature, and record which direction is dangerous for this reading, so future drifts are judged against a known target.

High One alarm setting causing alarm floods all week Dairy 1,271 alarms in a week

What was found

The CIP-1 caustic strength Low alarm activated 1,271 times in the week, and 154 bursts of chatter held 587 of those activations (46.2%).

The evidence

One setting causes 1,271 alarms a weekCIP-1 caustic strength Low alarm: 10-minute periods over the flood threshold, per dayA flood is more than 10 alarms in 10 minutes. This alarm has a deadband of 0 and no delay. The first and last days are part days.
051015Alarm floods per dayNov 2: 8 alarm floods8Nov 2Nov 3: 16 alarm floods16Nov 3Nov 4: 10 alarm floods10Nov 4Nov 5: 7 alarm floods7Nov 5Nov 6: 13 alarm floods13Nov 6Nov 7: 10 alarm floods10Nov 7Nov 8: 11 alarm floods11Nov 8Nov 9: 3 alarm floods3Nov 978 alarm floods in one week, every one led by this alarmWorst 10 minutes: 19 alarms, on Nov 4. A healthy alarm system has no floods.051015Alarm floods per dayNov 2: 8 alarm floods8Nov 2Nov 3: 16 alarm floods163Nov 4: 10 alarm floods104Nov 5: 7 alarm floods75Nov 6: 13 alarm floods136Nov 7: 10 alarm floods107Nov 8: 11 alarm floods118Nov 9: 3 alarm floods3978 alarm floodsin one weekNormal:none

Redrawn from the live finding, Nov 9, 2026. Open the real finding

Why it matters

The alarm trips below 30.0 with a deadband of 0.0 and no on-delay or clear delay, so a value hovering near the setpoint re-triggers it repeatedly. 78 of 998 active 10-minute periods exceeded the threshold of 10 activations; the peak was 19.

What to do now

Check the CIP-1 caustic strength reading for noise or a value sitting near 30.0, and acknowledge the repeat alarms knowing they are one condition.

How to prevent it

On the UDT type member CausticStrength|Low, add a clear delay of 15 s and a deadband, so the value must move back past the setpoint before the alarm clears. Check the effect on CIP-2, which shares the type.

Short videos

See it in 30 seconds

Four findings from plants running Artekis, each shown on the finding screen your team would use.

Treated water turning cloudyArtekis catches the climb a day and a half in. No alarm is set on this reading.
Scrap that rose while every signal looked fineA die-casting press whose metal temperature ran outside its ±5 °F band 23% of running time, up from 1%, and the $9,258 of scrap above its own normal.
A silo reading that dropped 2.4 °F and stayedA raw milk silo reading that dropped about 2.4 °F and stayed there, with no alarm. Milk or probe? One sensor cannot say, so Artekis says to check it with a handheld.
One alarm, 1,271 activations in a weekA clean-in-place alarm that went off 1,271 times in one week, and the setting that fixes it.
Pick your plant

What it would find on yours

The same module runs on every plant. What changes is what it watches and what a miss costs you.


What it is

A module inside your Ignition gateway

It watches every measurement against its own normal, reviews your alarms, explains stops, checks the gateway, and answers questions in plain English. Every finding lands on one list in Perspective, in plain words, with the machine it is about, what to do now and the evidence behind it. Each change is a recommendation; your engineers decide what to apply.

Finds what nobody knew to askA slow climb, a stuck reading or a pump losing flow, each judged against that machine’s own normal for what it is doing right now.
Explains the stopThe minutes before a stop on one page: the first alarm, the change someone made, the likely cause and what to check first.
Cleans up the alarm listWhich alarms waste your operators’ time, and the one setting that fixes each, written in Ignition’s own property names.
Your engineers decideThey confirm or dismiss each finding, with a name on every verdict, and a finding closes itself when the data shows the fix held.

What it finds, analysis by analysis →

Ask your plant

“Which press lost the most time this week, and why?”

Your supervisors type a question beside the Perspective screens they already use. The answer comes back in minutes and dollars, with the records behind every claim. An answer that cannot cite its source says so instead of guessing.

Ask your plant1:14Scrap jumped on a press with no alarm. The supervisor asks the press, and the answer names the setpoint change, when it was made and the data behind each claim, then looks ahead to the next press heading for trouble.
Which press are the leak-test rejects in machining coming from?
The answerCastings from press DCM-304 while its shot sleeve wore: 3.6% failed leak test, against 1.0 to 1.7% for every other press.
Only possible because the press and the machining cell live in one gateway
Which cell waits on castings the most?
The answerCell ML-3: 28 waiting-on-castings stops and 1,960 minutes in 60 days, against 6 stops on ML-1.
From the downtime table, through a query your team approves
Artekis in a Perspective session: the jet-cool finding on press DCM-302 with what was found, why it matters, what to do now and the evidence table, and the Ask panel answering the finding’s own follow-up question
A die-casting plant running Artekis: the jet-cool finding on press 302 and the Ask panel answering “what is the likely cause, what should I do about it, and how do I check the fix worked?” Click to open full size.

Both answers are from a die-casting plant running Artekis. Ask reads your production database only through named queries your team writes, so IT decides exactly what it can see.


Read-only by design

Every model call is on record with its price.

  • Read-only by design. Artekis reads tags, history, alarms, the audit log and the named queries you allow. A proposed change goes to your engineers, who apply it under your own change control.
  • What leaves the gateway. Only the evidence for one run or one question, sent with your own model key from Ignition’s Secret Provider to the provider you choose. With a model on your own network, nothing leaves it.
  • Every call recorded with its price. The Cost and Egress pages list each model call, its price and every message sent. Show prompt displays exactly what a run would send, at no cost.
  • Stored in your database. Findings, evidence and verdicts are kept in your SQL Server, MariaDB, MySQL or PostgreSQL.
Who built it

From the team that builds Ignition systems

Artek is an Ignition integrator and an Inductive Automation Premier Integrator, founded in 2020 by Jerry Eppler and Jae Park, both former Inductive Automation engineers. We build the kind of Ignition systems Artekis analyzes, for water utilities, data centers, manufacturers and energy companies.

Visit artekis.io →

$10,000$7,000one-time, per gateway, engineer included2026 price, through December 31, 2026

One license covers every analysis on one gateway, with annual support for updates, the same model as Ignition. It includes four hours of an Artek engineer’s time to install it with your team, draft your plant model, run your first reports, and show your supervisors how to ask questions it answers well. There is no cloud service to subscribe to; model usage is paid to your provider, in cents.

Annual support is 20% of what you paid for the license, so $1,400 a year on a 2026 purchase instead of $2,000.

Ask for a price on several gateways →   Pricing in detail →

Questions

Common questions

Does Artekis change anything on our gateway?+

Artekis is read-only. It reads tags, history, alarms and the audit log, and writes its findings to its own tables in your database. A proposed change is a recommendation your team applies under its own change control.

Can it answer questions from our production database, like scrap or downtime?+

Yes, through named queries. Your team writes a select-type named query in a project Artekis is allowed to read, and Ask can call it, up to 1,000 rows at a time. Ask runs only those queries, so your IT team decides exactly what the model can see.

Which AI model does it use?+

One you choose, through your own key: Anthropic, OpenAI, or any OpenAI-compatible endpoint, including a model you run on your own network. Every call is priced and recorded.

We were asked about Microsoft Copilot. How does Artekis compare?+

Copilot works on Microsoft 365 data and cannot see an Ignition gateway. Artekis runs inside the gateway and reads your tags, history, alarms, audit log and production database directly, then sends only the evidence for one question or one run to the model you choose. It answers in Perspective, where your supervisors already are, with a citation for each claim.

Which Ignition versions does it support?+

Ignition 8.3. The module loads on 8.3.4 and later, and 8.3.8 is the verified platform.

How is it licensed, and what does it cost?+

A one-time license per gateway, normally $10,000 and $7,000 for purchases through December 31, 2026, activated through Ignition’s own licensing, with an annual support plan for updates and new releases, the same model as Ignition. The price includes four hours of an Artek engineer’s time to set it up with your team. You can evaluate it in Ignition’s two-hour trial first, and it is free on Maker Edition under Maker’s non-commercial terms.

Next step

Tell us about your gateway and what you want to find out.

A member of our team reads every message and replies, usually the same day.

Contact us →